Setting Parameters
01/02 AWB8230-1415GB
174
If SLV control is active, set the pulse frequency in PNU b083 to at
least 2.1 kHz (a Section Pulse frequency, Page 164). If the
motor drives a very small load, (i.e. has a low moment of inertia),
it may whip or jolt. If this is the case, do the following:
X Set the motor stabilization constant (PNU H006) accordingly
and reduce the pulse frequency (PNU b083).
X Deactivate the AVR function by entering 01 in PNU A081.