192
Ambient conditions
Ambient temperature 10 to +50 °C
From about +40 to +50 °C, the pulse frequency should be reduced to 2 kHz. The output current should be
less than 80 % of the rated current in this case.
Temperature/humidity during storage
25 to 70 °C (for short periods only, e.g. during transport)
20 to 90 % relative humidity (non condensing)
Permissible vibration
Up to 5.9 m/s
2
(= 0.6 g) at
10 to 55 Hz
Up to 2.94 m/s
2
(= 0.3 g) at 10 to 55 Hz
Installation height and location
Maximum 1000 m above sea level in a housing or control panel (IP54 or similar)
Optional accessories Remote operating unit: DEX-KEY-10
Choke to improve the power factor
DE6-LZ...-V4 RFI filter
Expansion modules
Encoder module: DE6-IOM-ENC
PROFIBUS-DP module: DE6-NET-DP
DV6-340-...
22K 30K 37K 45K 55K 75K 90K 110K 132K
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616