Installation
01/02 AWB8230-1415GB
42
If a relay is connected to one of the digital outputs 11 to 15 or 12,
connect a free-wheel diode in parallel to the relay to prevent
destruction of the digital outputs through the self-induced e.m.f.
which results when the relay is switched off.
Figure 35: Relay with free-wheel diode
h
Use relays that switch reliably at 24 V H and a current of
about 3 mA.
h
Route the control and signal cables separately from the
mains and motor cables.
+ 24 V
250 mA
CM2 1211 15
Figure 36: Crossover of signal and power cables
a Power cable: L1, L2, L3, U, V, W, L+, DC+, DC, R0, T0
b Signal cables: H, O, OI, O2, L, FM, AM, AMI,1 to 8, 11 to 15, CM1,
CM2, P24, TH, K11, K12, K14
f 100
ba
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

Table of Contents