44 of 82 MANUAL-75-v2.0
Tip
A green indicator light means that a ground fault circuit interrupter
(GFCI) outlet has not tripped.
8. Switch all breakers to the
OFF
position.
9. Turn the
Control
knob to the
OFF
position.
If required, cables can be adjusted in
OFF
or
STANDBY
.
3.9 Using auto start and stop
MP75-600 has an auto start and stop functionality that automatically engages a
supplemental diesel generator to charge the unit battery.
If the unit battery charge is at 30%, the unit signals the connected generator to start
charging. When the unit battery charge reaches 90%, the unit signals the connected
generator to stop charging.
Notice
To be able to charge the unit with a supplemental generator, make sure you
connect the charger from the generator to the unit's charge port.
► For more information, see
Charging connection
on page 31
To use the auto start and stop functionality, follow these steps:
1. At the back of the unit, locate the bottom right panel door.
2. If needed, unlock the panel door with the supplied keys, and then pull the latch to
open the door.
3. On the bottom right panel, connect the supplied control cable (PN P0002044-01)
to the
GENERATOR AUTO START
port.
► For more information, see
Cam-lock connections
on page 30
4. Connect the other end of the control cable to the auto start and stop terminal
block of a supplemental diesel generator.
Make sure the wiring is correct.
MP75-600 - User Manual 3 Quick start