MANUAL-75-v2.0 67 of 82
6 Troubleshooting
This section provides troubleshooting information and a list of common fault codes for
the unit.
Table 2 - Troubleshooting issues
Symptom Possible cause Solution
The unit turns on
but will not
transition to
RUN
.
The emergency stop button is
depressed.
Release the emergency stop
button and cycle the control
knob from
STANDBY
to
RUN
.
The battery is fully discharged. Plug in and charge the unit.
The twist-lock
outlets do not work
in the 240 V mode.
The incorrect twist-lock outlet is
being used. Twist-lock outlet 3 is
not available in the 240 V mode.
Disconnect the twist-lock plug
from the twist-lock outlet 3
and connect the twist-lock
plug to the twist-lock outlet 1
or 2.
Main circuit breaker and/or twist-
lock circuit breaker are in the
OFF
position.
Set the main circuit breaker
and/or the twist-lock circuit
breaker to the
ON
position.
The twist-lock
outlets do not work
in the 480 V mode.
In the 480 V mode, twist-lock
outlets are disabled to prevent
unintended over-voltage of lower
voltage loads.
N/A
The outlets in the
Outlet Panel are
powered but the
main circuit breaker
is
OFF
.
The outlets in the Outlet Panel are
powered by a separate inverter
and are only turned off through
the Outlet Panel circuit breakers.
N/A