64 of 82 MANUAL-75-v2.0
5.6 Isolating the high voltage system for internal
maintenance
WARNING
Risk of serious injury or death!
The high voltage system must not be disconnected by any personnel unless
they have Moxion Power Training Certification.
The internal systems, battery, and electrical connections are high voltage. Before
doing any maintenance on any of the internal components of the unit, the high voltage
systems need to be isolated.
WARNING
Risk of electrical shock!
Engaging the e-stop does NOT isolate the internal high voltage systems.
To isolate the system from high voltage, the system needs to be in
SERVICE MODE
.
To isolate the high voltage, follow these steps:
1. Set the unit status to
STANDBY
.
2. Make sure all switches are turned
OFF
.
3. Turn
ON
switch 4.
4. Turn
ON
switch 5.
5. Turn
OFF
switch 5.
6. Turn
OFF
switch 4.
7. Turn
ON
switch 5 for 3 seconds.
8. Turn
OFF
switch 5.
9. Confirm
SERVICE MODE
is shown on control display.
MP75-600 - User Manual 5 Service and maintenance