56 of 82 MANUAL-75-v2.0
4.6
How to set up an earth connection
WARNING
Risk of electrical shock!
CONNECTING THE GROUND.
Only qualified and trained electricians that know local electrical and safety
code guidelines must connect the required ground connections.
Consult with local Electrical and Safety Codes for proper connection based
on condition of use.
The Occupational Safety and Health Administration (OSHA) and the National
Electrical Code (NEC) recommend that if the unit is providing electrical
power to a structure, for example, home, office shop, trailer or similar, it must
be connected to a grounding electrode system, such as a driven ground rod.
For more information about ground connections, contact Moxion Power.
Call 1-833-669-4661 or customersupport@moxionpower.com.
MP75-600 - User Manual 4 Operations
4.7 How to set up a ground rod
WARNING
Risk of electrical shock!
BEFORE OPERATING THE MPU.
REFER to Article 250 (Grounding and Bonding) of National Electrical Code
(NEC) for guidance on generator grounding, including the Conductor
Grounding Table for appropriate ground conductor sizing.
CHECK with all relevant governing bodies on electrical grounding
requirements for generators.
IF conditions of use require a grounding rod, ENSURE the ground rod
installation is done in accordance to the above guidelines & requirements
MPU bring-up & ground rod installation activities shall ONLY be performed
by qualified personnel.
For more information about ground connections and examples of
appropriate installations contact Moxion Power.
Call 1-833-669-4661 or customersupport@moxionpower.com.