Instructions 
 
  Page 87 
12.12. Template: HELIccpm 
suitable for: 
  Main rotor control systems with electronic mixers 
CCPM (Cyclic-Collective-Pitch-Mixing) 
with 3 or 4 servos, 90° to 150° 
Typical models: 
  ECO 8, Logo, Fury, Three Dee NT, Uni-Expert 
12.12.1. Assigned transmitter controls and switches 
Assignment used:  HELI 
 
A : Sum timer ´ controlled by THR.LIMITER (F) 
 Dual-Rates Direct Main Throttle 
 A/E/R Throttle phase CUT
 
  OFF  OFF  OFF 
 
Phase 1-3 Gyro Thr. limiter (Direct Thr.) 
1: HOVER  Centre  Minimum 
12.12.2. Assigned servos / receiver outputs 
The default setting in the HELIccpm model template is a 
120° swashplate with the pitch-axis servo at the rear. 
 
 
12.12.3. Fine-tuning 
a. Check stick functions (roll, pitch-axis, yaw) 
Select different mode if necessary (è 13.3.1.) 
L, Assignment, Mode 
b. Check direction of servo rotation for all functions 
If necessary change servo direction (REVERSE) 
K, Calibrate, select servo, Parameter REV/CLR 
c. Gyro features 
è 15.3. 
13.  Main menu „Setup“ L 
This main menu is primarily concerned with settings 
which apply to the transmitter generally. 
 
ü  This symbol indicates global settings which influ-
ence the behaviour of the transmitter generally. 
I  Some settings apply only to the selected model. 
These are marked with the model memory symbol. 
13.1. Sub-menu „Transmitter“ 
13.1.1. Parameter „Trim graphics“ 
ü  global effect 
The current state of the trims can be displayed on 
screen in any of 6 different ways (trim graphics 0 to 5). 
We suggest that you try out the variants and set the one 
which you find easiest to see at a glance. 
13.1.2. Parameter „Sounds“ 
ü global effect 
With this parameter you determine which events in the 
transmitter trigger an audible signal. 
  Setting   Audible signal 
1. 
Battery 
when battery voltage 
falls below alarm threshold 
2. 
Batt+Time 
as 1. + timer alarm 
3. 
B+Ttim+Tr 
as 2. + trim adjustments  
4. 
Init off 
all, except during power on 
5. 
All 
always 
 
13.1.3. Parameter „Battery alarm“ 
ü  global effect 
Range 6,50 to 7,5 V (0,01V increments) 
Default setting 6,9 V 
The battery alarm is intended to alert you to a failing 
battery, i.e. the charge is only sufficient for a limited 
residual operating time. 
! The lower you set the threshold, the shorter the 
remaining residual operating time. 
The residual operating time varies very widely accord-
ing to the set threshold and the state of the battery. For 
this reason it is important that you should carry out a 
test to establish how much residual time is available in 
your particular case. 
This is done by switching on the transmitter with the 
aerial fully extended, and the RF module with crystal (or 
synthesizer) installed. You don’t need to move the 
sticks. Set the alarm threshold to the desired value, and 
leave status display 1 or 2 on the screen to show the 
battery voltage. 
Now time the period from the first audible alarm warn-
ing until the minimum operating voltage (6.5 V) is 
reached). 
! The transmitter switches itself off automatically 
at around 6.3 V!