17
PROGRAMMING
NESS D8 (V4.7) CONTROL PANEL – INSTALLER MANUAL
DOUBLE TRIGGER ZONES
Zones programmed to Double Trigger will recognise an alarm condition if:
• The zone has been triggered twice within a 4 minute period.
• If any 2 zones (both programmed for double trigger), each trigger once.
• The zone is left unsealed for longer than 15 seconds.
PROGRAMMING SEQUENCE:
P39E [Zone No]E toggles the options ON and OFF
P39E [Zone No]E OFF: The zone is not a Double Trigger zone
P39E [Zone No]E ON: The zone is a Double Trigger zone
P39E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No Double Trigger zones
NOTES:
Double Trigger is useful for preventing
unwanted alarms from zones in harsh
environments such as sheds and
garages.
0E will turn all selections OFF
MEMORY E will turn all selections ON
INSTANT ZONES
Instant Zones operate only in the Armed state. When Armed at the expiry of exit
time, Instant Zones will activate assigned out puts immediately when triggered.
P40E [Zone No]E turns the options ON
P40E [Zone No]E ON: The zone is an Instant Zone
To deselect the option, select a different zone type in the DELAY GROUP.
P40E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
3E–8E ON: Zones 3~8 are Instant
NOTES:
When a zone is selected for this type, it is
automatically deselected from any other
zone type in the DELAY GROUP
ENTRY DELAY1 ZONES
Entry Delay1 zones operate only in the Armed state. When Armed, at the expiry
of exit time these zones will activate the Entry Delay Timer1 (P26E) when they are
triggered. If the panel is not disarmed before the expiry of the Entry Delay Timer1,
the alarm outputs will be activated.
P41E [Zone No]E turns the options ON
P41E [Zone No]E ON: The zone is an Entry Delay1 zone
To deselect the option, select a different zone type in the DELAY GROUP.
P41E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
1E ON: Zone 1 has Entry Delay1
NOTES:
The keypad sonalert will beep during
Entry Delay as a reminder to disarm the
panel. Entry beeps can be disabled by
program option P60E 1E.
When a zone is selected for this type, it is
automatically deselected from any other
zone type in the DELAY GROUP
OPTION No DESCRIPTION 1 2 3 4 5 6 7 8
Zones
ON = Factor
y
default settin
g
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ONONONONONON
ON
ON
ON
ON
ON
ON
ON
ON
P39E
P40E
P41E
P42E
P43E
P44E
P45E
P46E
P51E
P52E
P53E
Double Trigger zones
Instant zones
Entry Delay 1 zones
Handover zones
Entry Delay 2 zones
Lockout zones
Area 1 zones
Area 2 zones
Monitor zones
24Hr zones
Day zones
DELAY GROUP
Only one option
allowed per zone
ZONE ASSIGNMENT

Table of Contents