PROGRAMMING
NESS D8 (V4.7) CONTROL PANEL – INSTALLER MANUAL
OPTION No DESCRIPTION DEFAULT NOTE
P91E Required Rings to answer 1
SEND DIALLER TEST REPORT
Send a Dialler Test Report to the telephone numer programmed at P70E.
This test operates only in User program mode.
P66666666E (eight 6’s) Triggers dialler and sends test report to Central Station
SIREN TEST
Turn the Siren, Reset and Strobe Outputs On. Pressing P E will stop the Siren Test (and also
exits Program Mode).
This test operates in User and Installer program mode.
P77777777E (eight 7’s) Triggers Siren, Reset, Strobe
PANEL RESET
This function resets the microprocessor. The effect is the same as powering down and
powering up again. Panel Reset operates in User and Installer program mode.
P88888888E (eight 8’s) Panel Reset
PANEL SOFTWARE VERSION
This function displays the panel software version when in program mode. Displayed in
decimal format by the zone LEDs.
Example, version 4.5 is displayed by fl ashing 4 followed by 5.
This test operates in User and Installer program mode.
P999999999E (eight 9’s) Displays software version
OPTION No DESCRIPTION 1 2 3 4 5 6 7 8
Zones
P94E
"No memory warning" zones
SPECIAL FUNCTIONS
NO MEMORY WARNING ZONES
Select zones 1 to 8 that do not fl ash the Memory indicator on the keypad/s. The
alarm still goes into memory and can be seen when reviewing.
PROGRAMMING SE QUENCE:
P94E 1E-8E toggles the option ON and OFF
P94E 1E-8E OFF: Memory Warning operates normally for that zone
P94E 1E-8E ON: Memory Warning is disabled for that zone
P94E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
no zones selected
NOTES:
0E will turn all selections OFF
MEMORY E will turn all selections ON
REQUIRED RINGS
Sets the number of double-rings before an incoming call is answered. This is used
for Remote Access.
Programmable from 1 to 16 rings. Enter a value between 1 and 16.
PROGRAMMING SEQUENCE:
P91E existing Required Rings value is displayed
[ENTER NEW VALUE] E new Required Rings value is displayed
P91E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
1
NOTES:
RELATED OPTIONS:
P90E 1E to 8E (Remote Access options)