FORCED OPENING REPORT
If Forced Opening Report is selected ON – when an alarm has been reset by a valid
User Code (or Radio Key), the dialler will send an Opening report along with a restoral
report for the zone or miscellaneous input which caused the alarm.
PROGRAMMING SEQUENCE:
P88E 5E toggles the option ON and OFF
OFF: No Forced opening Reports
ON: Forced opening Reports enabled
P88E 5E
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
ON.
NOTES
This option is used to indicate to the
Central Station that an alarm has been
reset by a valid user. Usually used in
cases where Open/Close reports are
normally not sent.
MANUAL EXCLUDE REPORT
Enables Manual Exclude Reports for zones. Exclude Reports for 24hr zones are sent
on exiting EXCLUDE mode.
PROGRAMMING SEQUENCE:
P88E 7E toggles the option ON and OFF
OFF: No Manual Exclude Reports
ON: Manual Exclude Reports enabled
P88E 7E
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
ON.
RELATED OPTIONS
P88E 8E Auto Exclude Reports.
AUTO EXCLUDE REPORT
Enables Auto Exclude Reports for Zones. Zones not sealed on arming will be reported
as Auto Excluded..
PROGRAMMING SEQUENCE:
P88E 8E toggles the option ON and OFF
OFF: No Auto Exclude Reports
ON: Auto Exclude Reports enabled
P88E 8E
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
ON.
RELATED OPTIONS
P88E 7E Manual Exclude Reports.
AREA1 OPEN/CLOSE REPORTS
Enables or disables sending of AREA1 Open/Close reports. The User ID of the code
used is included in the report. Keyswitch arming is identified as User 16. Shortcut
arming is identified as User 17.
PROGRAMMING SEQUENCE:
P88E 1E toggles the option ON and OFF
OFF: No AREA1 Open/Close reports
ON: AREA1 Open/Close reports enabled
P88E 1E
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
OFF .
AREA2 OPEN/CLOSE REPORTS
Enables or disables sending of AREA2 Open/Close reports.
PROGRAMMING SEQUENCE:
P88E 2E toggles the option ON and OFF
OFF: No AREA2 Open/Close reports
ON: AREA2 Open/Close reports enabled
P88E 2E
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
OFF.
AREA1 open/close report
AREA2 open/close report
Forced opening report
Manual exclude report
Auto exclude report
Option No. Description
1E 2E 3E 4E 5E 6E 7E 8E
P88E
OPEN/CLOSE REPORTING OPTIONS
ON ON ON
41
Ness eCO8x CONtrOl PaNel – INstallatION MaNual
P R O G R A M M I N G