4.13.1 Minimum resistances and power ratings for the braking resistor at 40 °C (104 °F)
Table 4-20 Braking resistor resistance and power rating (200 V)
Table 4-21 Braking resistor resistance and power rating (400 V)
* Resistor tolerance: ±10 %
Overload protection
When an external braking resistor is used, it is essential that an overload protection device is incorporated in the braking resistor circuit;
this is described in Figure 4-23 Typical protection circuit for a braking resistor on page 110.
Model
Minimum resistance * Instantaneous power rating Continuous power rating
kW kW
03200106 20 8.5 3.6
04200137
18 9.4
4.6
04200185 6.3
05200250 16.5 10.3 8.6
06200330
8.6 19.7
12.6
06200440 16.4
07200610
6.1 27.8
20.5
07200750 24.4
07200830 4.5 37.6 32.5
08201160
2.2 76.9
41
08201320 47.8
09201760
1.2 144.5
59.4
09202190 79.7
10202830
1.3 130
98.6
10203000 116.7
Model
Minimum resistance * Instantaneous power rating Continuous power rating
kW kW
03400025
74 9.2
1.5
03400031 2.0
03400045 2.8
03400062 4.6
03400078
50 13.6
5.0
03400100 6.6
04400150
34 19.9
9.0
04400172 12.6
05400220 31.5 21.5 16.2
05400270 31.5 21.5 16.2
05400300 18 37.5 19.6
06400350
17 39.8
21.6
06400420 25
06400470 32.7
07400660
9.0 75.2
41.6
07400770 50.6
07401000 7.0 96.6 60.1
08401340
4.8 140.9
81
08401570 98.6
09402000
2.4 282.9
118.6
09402240 156.9
10402700
2.6 260
198.2
10403200 237.6
11403770 1.83 369.4 185
11404170 1.2 563.4 200
11404640 1.2 563.4 250