4.7 Position feedback interface
The following functions are supported on the 15-way high density D-type connector on the drive:
• Position feedback interface
• Encoder simulation output.
• Motor thermistor input.
The position feedback interface is always available however the encoder output simulation depends on the position feedback device selected
Figure 4-15 Location of position feedback interface
51 0V
52 +24 Vdc
Size 6
Nominal operating voltage + 24.0 Vdc
Minimum continuous operating voltage + 18.6 Vdc
Maximum continuous operating voltage + 28.0 Vdc
Minimum startup voltage + 18.4 Vdc
Maximum power supply requirement 40 W
Recommended fuse 4 A @ 50 Vdc
Size 11
Nominal operating voltage + 24.0 Vdc
Minimum continuous operating voltage + 19.2 Vdc
Maximum continuous operating voltage + 30 Vdc
Minimum startup voltage + 21.6 Vdc
Maximum power supply requirement 60 W
Recommended fuse 4 A @ 50 Vdc
To prevent the risk of a fire hazard in the event of a fault, a fuse or other over-current protection must be installed in the relay circuit.
5
10
15
1
6
11
Drive encoder connector
Female 15-way D-type
Front view Underside
view