Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
User Menu A Commissioning
Advanced
Parameters
Diagnostics Optimization CT MODBUS RTU Technical Data
Installation and System Design Guide 27
Issue Number: 1
2.10.3 Compact external EMC filters
The external Compact EMC filter for size 3, 4 and 5, drives can be bookcase mounted, the details for each of the Compact EMC filters is provided
following.
Table 2-14 External Compact EMC filter data (frame size 3 to 5)
N
When using the external Compact EMC filters an additional AC input line reactor is required which is selected to meet the requirements of
EN12015:2014.
2.11 EMC compliance (general standards)
This is a summary of the EMC performance of the drive. For full details, refer to the EMC Data Sheet which can be obtained from the supplier of the
drive.
Table 2-15 Immunity compliance
1
See section 4.17.8 Surge immunity of control circuits on page 121 for control ports for possible requirements regarding grounding and external
surge protection
Emission
The drive contains an in-built filter for basic emission control. An additional optional external filter provides further reduction of emission.
The requirements of the following standards are met, depending on the motor cable length and switching frequency.
Model CT part number
Weight
kg lb
400 V
03400025 to 03400100
4200-6126 0.4 0.88
4200-6219 0.6 1.32
04400150 to 04400172 4200-6220 0.7 1.54
05400270 to 05400300 4200-6221-01 1.7 3.75
Standard Type of immunity Test specification Application Level
IEC61000-4-2 EN61000-4-2 Electrostatic discharge
6 kV contact discharge
8 kV air discharge
Module enclosure
Level 3
(industrial)
IEC61000-4-3
EN61000-4-3
Radio frequency radiated field
10 V/m prior to modulation
80 - 1000 MHz
80 % AM (1 kHz) modulation
Module enclosure
Level 3
(industrial)
IEC61000-4-4
EN61000-4-4
Fast transient burst
5/50 ns 2 kV transient at 5 kHz repetition
frequency via coupling clamp
Control lines
Level 4
(industrial harsh)
5/50 ns 2 kV transient at 5 kHz repetition
frequency by direct injection
Power lines
Level 3
(industrial)
IEC61000-4-5
EN61000-4-5
Surges
Common mode 4 kV
1.2/50 s waveshape
AC supply lines:
line to ground
Level 4
Differential mode
2 kV
1.2/50 s waveshape
AC supply lines:
line to line
Level 3
Lines to ground
Signal ports to ground
1
Level 2
IEC61000-4-6
EN61000-4-6
Conducted radio frequency
10V prior to modulation
0.15 - 80 MHz
80 % AM (1 kHz) modulation
Control and power lines
Level 3
(industrial)
IEC61000-4-11
EN61000-4-11
Voltage dips and interruptions
-30 % 10 ms
+60 % 100 ms
-60 % 1 s
<-95 % 5 s
AC power ports
IEC61000-6-1
EN61000-6-1:2007
Generic immunity standard for the residential, commercial and light -
industrial environment
Complies
IEC61000-6-2
EN61000-6-2:2005
Generic immunity standard for the industrial environment
Complies
IEC61800-3
EN61800-3:2004
Product standard for adjustable speed power drive systems (immunity
requirements)
Meets immunity requirements for first and second
environments