F1: Program Mode
42-02-2M01 A1 4-17
4
Motion 4000
Fire Service Menu Options
FIRE SERVICE OPERATION?
If Fire Service operation is not required, set to NO. If set to YES, the options below will
appear.
FIRE PHASE 1 MAIN FLOOR
Any landing may be the Main Fire Return Floor for Fire Service.
FIRE PHASE 1 ALT. FLOOR
Any landing may be the Alternate Fire Return Floor for Fire Service.
•FIRE SVCE. CODE
Fire Service Operation will conform to the selected fire service code. Available codes:
1. CHICAGO (OLD) 12. MASSACHUSETTS
2. VET ADMIN (Veterans' Administration) 13. ANSI A17.1 85-88
3. NYC RS-18 14. CITY OF DENVER
4. ANSI A17.1 -89> 15. CHICAGO 2001
5. CALIF. TITLE 8 16.. ANSI A17.1 -2000
6. HAWAII 17. BRITISH STANDARD
7. CSA B44-M90 18. ANSI A17.1a 2005
8. 34 PA CODE, CH. 7 19. ANSI A17.1-2007
9. CITY OF HOUSTON 20. ANSI A17.1-2012
10. AUSTRALIA 21. ANSI A17.1-2016
11. CITY OF DETROIT
FIRE PHASE I 2ND ALT. FLOOR
Detroit Fire Code only. Any landing may be the 2
nd
alternate fire return floor.
Select None if there is no second alternate return floor.
WILL THIS CAR RUN ON PH2?
If set to yes, this car is allowed to run on Fire Phase II.
BYPASS STOP SW. ON PHASE 1?
Prevents the stop switch from being bypassed on Fire Phase I. When set to NO, the
CSB output will not come ON as the car is returning on Fire Phase I.
HONEYWELL FIRE OPERATION?
Only if FIRE SVCE. CODE option set to AUSTRALIA (See “FIRE SVCE. CODE” on
page 4-17). If set to YES, Australia fire code will conform to Honeywell requirements.
If set to NO, controller will conform to standard Australia code.
NYC FIRE PHASE 2 AND ANSI 89?
Available only if FIRE SVCE. CODE is set to ANSI A17.1 89 (See “FIRE SVCE. CODE”
on page 4-17). If set to YES, ANSI A17.1 89 Fire Code will conform to New York City
Fire Code requirements when on Fire Phase 2. If set to NO, controller will conform to
standard ANSI A17.1 89 Fire Code.