Initial Power Up
42-02-2M01 A1 2-15
2
Motion 4000
Often Used Procedures
Following are some procedures and techniques that are often used while setting up drive and
controller parameters:
How to check Car Speed:
1. Place Function Switch F3 on the MPU board in the ON (up) position.
2. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
3. Press the S push button to select the menu.
4. Press the N push button until POSTN and SPEED are displayed.
5. Run the car. Speed is displayed in feet per minute.
How to place the car on Inspection Mode Fault Bypass:
1. On the MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL board, use a jumper to short the pins of JP1 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until INSPECTION MODE FAULT BYPASS is scrolled on the
display.
6. Press the S push button to change the setting to BYPASS ON.
Inspection mode fault bypass remains activated, even across power cycles, until switched off.
Note
In the F3 menu, Automatic Mode Fault bypass is just before Inspection Mode Fault bypass.
When you want Inspection Mode bypass, be careful you do not mistakenly set Automatic mode.
How to place the car on Automatic Mode Fault Bypass:
1. On the MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL board, use a jumper to short the pins of JP1 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until AUTOMATIC MODE FAULT BYPASS is scrolled on the
display.
6. Press the S push button to change the setting to BYPASS ON.
Automatic mode fault bypass times out after two hours.