GC2e Wireless Security System | Installation and Programming Guide
©2020 Nortek Security & Control LLC. All rights reserved. 43 2GIG is a registered trademark of Nortek Security & Control LLC.
Q: Select Wired Sensor# Equipment Type
DEFAULT: Varies by wired sensor type
NOTE: This queson is only displayed when certain sensor types
(zones) are selected.
The equipment type selecon will aect the sensors extended
reporng code.
The following sensor types require equipment type selecon:
Q: Select Wired Sensor# Normal State
DEFAULT: (0) Not Used
The two hardwired loops can be wired for normally open (N/O) or
normally closed (N/C) contacts, or for end-of-line (EOL) resistor.
The default seng (0) Not Used disables this wired sensor.
To use this wired sensor, select the way the loop is wired:
Wired Sensor Normal State
(0) Not Used
(1) Closed
(2) Open
(3) End‐of‐Line Resistor
Q: Select Wired Sensor# Dialer Delay (0 to 1)
DEFAULT: (1) Enabled
If this feature is enabled, the delay me must be set to a minimum of
30 seconds for ANSI/SIA compliance. To set the delay me, see “Q35:
Abort Window Dialer Delay (0-2)” on page 52.
Wired sensors can trigger the digital communicator immediately or
aer a delay.
The default seng (1) Enabled causes delayed dialing for this
wired sensor number.
For immediate dialing for this wired sensor number, select (0)
Disabled.
Q: Construct Wired Sensor # Voice Descriptor
DEFAULT: No Default
NOTE: For a list of voice descriptors, see Voice Descriptors” on
page 35.
The voice descriptors are the words the Control Panel will announce
for this wired sensor if this wired sensor is programmed for voice
annunciaon. Up to ve (5) words are allowed.
1. Tap Insert to place a word from the vocabulary into the data
entry eld.
2. Use the ← or → arrows to scroll through the words, or enter the
word’s three (3)-digit number.
3. Tap Insert again for the next word. Up to ve (5) words are
allowed.
4. To move between words, tap the Fwd and Back buons.
5. To remove a word, tap Delete.
Q: Select Wired Sensor# Reports (0 to 1)
DEFAULT: (1) Enabled
Wired sensors can be programmed to trigger a report to the Central
Staon or not.
The default seng (1) Enabled acvates reporng for this wired
sensor number.
To prevent reporng for this wired sensor number, select (0)
Disabled.
Q: Select Wired Sensor# Chime (00 to 13)
DEFAULT: (0) Disabled
Each wired sensor can be set to sound a “ding-dong” chime and/or
sound its voice descriptor when the sensor is triggered.
The default seng (0) Disabled inacvates the chime for this
wired sensor.
If a chime and/or voice is required for this wired sensor,
choose one of the other chime opons (next page):
Select the equipment type that matches the sensor equipment using
the ← or → arrows, or enter the equipment type number directly on
the keypad.
NOTE: This Control Panel does not provide auxiliary accessory output
power.
Connecng a hardwire PIR using equipment type “moon” will
require an external stand-alone baery backed-up power supply for
the PIR.
Q: Wired Sensor # Equipment Code (0-9999)
DEFAULT: (0 )
Select the four (4)-digit equipment code that corresponds to the
appropriate sensor model. See “Equipment Codes” on page 37.
Q: Select Wired Sensor# Equipment Age (0 to 1)
DEFAULT: (0) New
The Control Panel can be used with new or exisng wired sensors.
If this wired sensor is new for the installaon, leave the
default seng of (0) New.
If this wired sensor is already installed, select (1) Exisng.
Sensor Types (Zone) RF Sensors Wired Sensors
(04) Interior Follower Yes Yes
(05) Day Zone Yes Yes
(06) 24-Hour Silent Alarm Yes Yes
(07) 24-Hour Audible Alarm Yes Yes
(08) 24-Hour Auxiliary Alarm Yes Yes
(09) 24-Hour Fire Yes No
(10) Interior with Delay Yes Yes
(14) 24-Hour Carbon Monoxide Yes No
Sensor Type (Zone) Equipment Types
(04) Interior Follower (1) Motion
(2) Contact
(06) 24-Hour Silent Alarm (1) Contact
(11) Emergency
(07) 24-hour Audible Alarm (1) Contact
(11) Emergency
(08) 24-Hour Auxiliary (1) Contact
(6) Freeze
(8) Water
(10) Temperature
(11) Emergency
(10) Interior with Delay (1) Motion
(2) Contact
(23) No Response Type (1) Contact
(2) Motion
Installer Programming