GC2e Wireless Security System | Installation and Programming Guide
©2020 Nortek Security & Control LLC. All rights reserved. 52 2GIG is a registered trademark of Nortek Security & Control LLC.
Control Panel Programming
Q35: Abort Window Dialer Delay (0-2)
DEFAULT: (1) 30 Seconds
The default minimum seng for ANSI/SIA CP-01 compliance is 30
seconds.
The delay me can be increased to 45 seconds without aecng
ANSI/SIA CP-01 compliance only if the combinaon of Q35 and Q6
or Q7 does not exceed one (1) minute.
NOTE: The dialer delay can be disabled for each sensor without
aecng ANSI/SIA CP-01 compliance. See “RF Sensor Programming
Quesons” on page 39.
The system delays calling the Central Staon to allow the user
enough me to cancel a false alarm before it is reported.
• The default seng is (1) 30 Seconds.
• To change the seng, select (0) 15 Seconds or (2) 45 Seconds.
Q36: Burglary Bell Cutoff (0 to 4)
DEFAULT: (0) 4 Minutes
When a burglary alarm is triggered, the bell will sound unl the
burglary bell cuto me expires.
• The default seng for the burglary bell cuto is (0) 4 Minutes.
• To change the cuto me, select an opon below.
Burglary Bell Cutoff Time
(0) 4 Minutes
(1) 8 Minutes
(2) 12 Minutes
(3) 16 Minutes
(4) Unlimited
NOTE: The 24-hour Auxiliary Alarm Zone (08) does not follow the
burglary bell cuto me and will sound the Control Panel’s local
alarm unl a User Code is entered. The Auxiliary Alarm Zone does
not trigger the external siren (if used).
Q37: Fire Bell Cutoff (0-4)
DEFAULT: (0) 4 Minutes
When a re alarm is triggered, the bell sounds unl the re bell
cuto me expires.
• The default seng (0) 4 Minutes sets the burglary bell cuto
to four (4) minutes.
• To change the re bell cuto me, select an opon below:
NOTE: Aer the AC power alert is displayed or clears, the
AC power loss report or AC power restore report can be sent to
the Central Staon immediately, or at a random me, see Q39:
Random AC Loss Report Time.
NOTE: The Control Panel’s AC Power Icon immediately displays the
power status. See “AC Power ON/OFF” on page 25.
Q39: Random AC Loss Report Time (0-1)
DEFAULT: (1) Enabled
This feature allows the system to report AC power loss and AC
power restore at a random me of up to 45 minutes aer the
event occurs. This helps to reduce Central Staon congeson due
to a wide-spread power outage aecng many Control Panels at
once. The random AC power status report mer is triggered based
on the me set by Q38: Random AC Loss Report Time.
• The default seng (1) Enabled turns this feature ON.
• To turn this feature OFF, select (0) Disabled.
NOTE: The installer code must be unique from the master user
code and all other user codes.
Q43: Installer Code (4 or 6 Digits)
DEFAULT: 1561
The installer code is a unique code that installaon technicians use
to access the Installer Toolbox on the Control Panel.
• The default installer code is 1561.
• To change the installer code, enter a new four (4)- digit code.
IMPORTANT: If you change the installer code, always write it
down so that you can access the system later.
Q44: Lock Installer Programming (0-2)
DEFAULT: (0) Disabled
The installer programming lockout feature is provided to prevent
takeovers. The Control Panel can be set to limit an installer’s access
to programming quesons aer a period of 48 hours. The 48-Hour
Lockout mer starts when the installer exits System Conguraon
mode.
Three (3) opons are available:
• Unlimited full access to programming (no lockout).
• Limited access to programming aer 48 hours.
• No access to programming aer 48 hours The default seng
(0) Disabled selects unlimited full access to programming (no
lockout).
To deny access to programming aer 48 hours, select (1) No
Access to Programming.
If you select (2) Limited Access to Programming the installer will
be able to view, but not change the following aributes aer the
system has run for 48 hours, the Central Staon phone number,
Central Staon account number, lock installer programming,
download ID, and default lockout elds.
Aer the 48 hour lockout mer has locked out the system, the
mer can be reset through the cell radio or PC download by
remotely seng this queson to (0) or (2). Seng the opon to
(0) or (2) will restart the 48 hour lockout mer.
Fire Bell Cutoff Time
(0) 4 Minutes
(1) 8 Minutes
(2) 12 Minutes
(3) 16 Minutes
(4) Unlimited
Q38: Time to Detect AC Loss, in Minutes (0-30)
DEFAULT: (10) 10 Minutes
When AC power is lost, they system displays a power loss alert
aer the specied me length. When power is restored, the alert is
automacally cleared aer one (1) minute.