— 6-15 —
Figure 6-13 : Handy Terminal display (In normal state)
NSK MEGATORQUE
MS1A50-*****
E*****
:_ Differs with the system configuration.
6.6.3. Turning Servo on
Figure 6-14 : Power “ON” sequence
Timer
Turn on power
Action for alarm
Servo lock
Operating
Motor
Master controller
(User devise)
Driver Unit side
Initialization
DRDY open DRDY close
SVON
Input
operation
Action for alarm
condition
DRDY
Figure 6-15 : Power ON / SVON timing
2 sec. Approx.
* : It will take 30 milliseconds for the Driver Unit to receive the
operation command after SVON is inputted.
ON
30ms min. *
ON
ON
Control power
Main power
supply
DRDY output
SVON input
Operation
Home Return, etc.
Caution : Turn on the main power supply first, then the SVON input. When turn off the
main power supply, turn off SVON first. If the main power supply is turned off
in the servo-on state, the Driver Unit outputs the AC Line under-voltage alarm.
Once this alarm occurs it will not recover unless the power is turned on again.
◊ Figure 6-14 and 15 show timing of power “ON” and SVON.