3 Establish an SSH connection, and execute the sync command from the terminal that you con-
nected to.
4 Wait for at least 5 seconds and turn OFF the power supply.
Procedure to Download to the Built-in Flash Memory (Version 2.5 or Later)
For PMAC firmware revision version 2.5 or later, you can also use the following procedure to store
the user program into the built-in flash memory
.
1 Download the user program from the Power PMAC IDE.
2 At the Power PMAC IDE terminal, enter Sys.SyncSave=1.
3 At the Power PMAC IDE terminal, execute the save
command.
Wait until the save completed notification is displayed on the Power PMAC IDE.
4 At the Power PMAC IDE terminal, enter Sys.SyncSave=0.
5 Wait for at least 5 seconds and turn OFF the power supply.
4 Installation
4-3
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
4-1 Processing at Power ON and Power OFF
4
4-1-2 Power OFF Operation