Exchanging Data Using SCADA and Other Software Section 3-4
The contents of a CSV tag file is shown below.
Contents Setting range for ITEMs
HMI tags User link table tags OPC Server direct access
tags
Record number 1 to 65535
Function block file
name
Max. 6 characters FDAC + node number
LCU/LCB element
name
LCB05, LCB01, LCB03,
LCB05D, LC0011, LC0012,
LC0013
LCB05, LCB01, LCB03,
LCB05D
LCB05, LCB01, LCB05D,
LC0011, LC0012, LC0013
Tag name (representa-
tive tag)
16 characters max. (Unusable
characters: None)
Always LNK 16 characters max. (Unusable
characters: None)
Tag ITEM Fixed for each function block
item
Tag name from user link table Fixed for each function block
item
Tag comment 16 characters max. (Unusable
characters: None)
Tag comment from user link
table, 23 characters max.
(Unusable characters: None)
16 characters max. (Unusable
characters: None)
Tag type 0: Analog, 1: Contact
Data attribute (See note
1.)
1: Integer, U: Unit, 0: Contact 0: Contact, B: 1-byte data,
U: UINT, I: INT
Contact alarm tag 0: Normal, 1: Alarm 0 0
Scaling upper limit –5000 to 99999
(Example for DP position of 1: –500.0 to 9999.9)
–5000 to 99999
(Example for DP position of 1:
–500.0 to 9999.9)
Scaling lower limit –5000 to 99999
(Example for DP position of 1: –500.0 to 9999.9)
–5000 to 99999
(Example for DP position of 1:
–500.0 to 9999.9)
Decimal point position
(for scaling)
0 to 9
Unit Max. 8 characters (Unusable characters: None)
Data range upper limit –340680 to 330779 (When
scaling ±320% data with an
upper limit of 99999 and a
lower limit of –5000)
65535 (Fixed) –340680 to 330779 (When
scaling ±320% data with an
upper limit of 99999 and a
lower limit of –5000)
Data range lower limit –340680 to 330779
(When scaling ±320% data
with an upper limit of 99999
and a lower limit of –5000)
–32768 (Fixed) –340680 to 330779
(When scaling ±320% data
with an upper limit of 99999
and a lower limit of –5000)
Network address 0 to 127
Node address 1 to 32
Unit address 16 to 31, 225 225 16 to 31, 225
I/O memory area 0: CIO, 1: W, 2: H, 3: D, 4: E0, 5: E1, 6: E2 ..., 15: EB, 16: EC Always 99
I/O memory address 0 to 65535 0
Bit position 0 to 15 0
Function block model 0 to 999 –1 0 to 999
Block address 0 to 999 –1 0 to 999
ITEM number 0 to 999 –1 0 to 999