4. Setting the Unit (Unit Operation)
4-2
4.2 Settings (FUN Mode Operation)
Enter FUN mode to make measurement and recording settings on the Portable Power
Monitor.
4.2.1 Setting Item List
The following list shows the setting items available in FUN mode.
Display Item Display Setting Item Setting Value
Factory
Default
CLEAR
Ranking clear
A press of the REC key
displays "CLEAR".
Another press of the REC
key clears the ranking.
-
CYCLE
Recording
interval
1s (sec.)/2s/5s/10s/20s/
30s/1min.
This setting item is not
displayed when the
measurement mode is
HISPD.
1s
TIMER
(ON)
STRIG
Start trigger
OFF/TIME
OFF
STIME
Start time
00:00 to 23:59
00:00
ETRIG
End trigger
OFF/TIME/ELPSD
OFF
ETIME
End time
00:00 to 23:59
00:00
ELPSD
Elapsed time
0.05 (0 min. 5 sec.) to
999.59 (999 min. 59 sec.)
0.05
MODE
Measurement
mode
NORM/SLEEP/HISPD
The unit reset itself and
restarts when the MODE
key is pressed to change
the operation mode after a
set value is applied.
SLEEP
REC
Recording
mode
CONT/RING
CONT
INTEG
Integrated
power reset
interval
OFF/30min./1h (hrs.)/24h
"30min.": Integrated power is
reset to zero at 0 and 30 min.
of every hour; "1h": reset at 0
min. of every hour; "24h":
reset at 0:00 every day. The
integrated power up until the
moment of reset is recorded
in the ranking log before it is
cleared to zero.
After the INTEG setting is
changed, the unit resets itself
and restarts, clearing the
ranking, when the operation
mode is changed by pressing
the MODE key.
OFF
USECH
The number of
channels to
use
1CH/2CH/3CH
1CH
TYPE
Measured
circuit
The displayed items vary
depending on the number of
the channels to use.
3P3