6.4 MODBUS MEMORY MAP
Register
Address
Description
Register
Type
Data Range
Over
Range
Read/Write Comments
1
Total
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
2
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
3
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
4
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
5
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
6
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
7
Reset Aux Input
Count 1
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
8
Reset Aux Input
Count 2
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
9
Reset Aux Input
Count 3
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
10
Reset Aux Input
Count All
Coil NA NA
Turn coil ON (1) to reset total. Turn
coil to OFF (0)once reset is complete.
8 Aux Output 1 Coil NA NA
Relay # 1 closed. Turn coil to OFF
the commissioning menu.
9 Aux Output 2 Coil NA NA
Relay # 1 closed. Turn coil to OFF
the commissioning menu.
10 Aux Output 3 Coil NA NA
Relay # 1 closed. Turn coil to OFF
the commissioning menu.