EasyManua.ls Logo

Onicon F-4300 - Additional Hardware that May be Required; Working Environment; Maintenance; Serial Number

Default Icon
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F
-
4300 CLAMP
-
ON ULTRASONIC FLOW METER
ONICON Incorporated 727.447.6140 Page 9 onicon.com
1.7 MAINTENANCE
Periodically inspect the power cables, transducer cables, cable glands and the enclosure for signs of damage. Inspect
transducer installation and mounting hardware for loose connections or diminished ultrasonic couplant.
1.5 ADDITIONAL HARDWARE THAT MAY BE REQUIRED

mounting brackets to rigid conduit.
1.6 WORKING ENVIRONMENT

considerations must be observed in selecting a location for the meter:
The ambient operating temperature range is -5°F (-20°C) to 140°F (60°C).

Avoid installation locations that are close to strong sources of electrical interference.
Avoid installing the electronics enclosure in direct sunlight.
Avoid installation locations where the transducers will be exposed to vibrations in the piping system.
Always run transducer cables in dedicated conduit separate from signal and power cables.

1.8 SERIAL NUMBER
The serial number of your F-4300 is located outside and inside the enclosure. Transducers will be packaged inside the
enclosure they were calibrated with and will bear their own unique serial numbers. You should have one of these serial
numbers available when contacting ONICON for assistance regarding your meter.

Table of Contents

Other manuals for Onicon F-4300

Related product manuals