• Table 5-1 (page 5-21) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Single-phase, Low-voltage PDU
• Table 5-2 (page 5-21) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Three-phase, Low-voltage PDU
• Table 5-3 (page 5-22) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Single-phase, High-voltage PDU
• Table 5-4 (page 5-22) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Three-phase, High-voltage PDU
Table 5-1 (page 5-21) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a single-phase, low-voltage PDU.
Table 5-1 Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 20 24
A Module 1, phase
2
0 17 22
A Module 1, phase
3
0 19 24
B Module 1, phase
1
0 19 24
B Module 1, phase
2
0 17 22
B Module 1, phase
3
0 20 24
Table 5-2 (page 5-21) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a three-phase, low-voltage PDU.
Table 5-2 Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 32 40
A and B Module 1, phase
2
0 34 42
A and B Module 1, phase
3
0 32 40
Table 5-3 (page 5-22) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units