Table 5-5 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 20 24
A Module 1, phase
2
0 10 13
A Module 1, phase
3
0 0.1 0.2
B Module 1, phase
1
0 0.1 0.2
B Module 1, phase
2
0 10 13
B Module 1, phase
3
0 20 24
Table 5-6 (page 5-23) lists the threshold values for Oracle Exadata Database
Machine X4-2 Half Rack using a three-phase, low-voltage PDU.
Table 5-6 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 17 22
A and B Module 1, phase
2
0 19 24
A and B Module 1, phase
3
0 15 20
Table 5-7 (page 5-23) lists the threshold values for Oracle Exadata Database
Machine X4-2 Half Rack using a single-phase, high-voltage PDU.
Table 5-7 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 18 23
A Module 1, phase
2
0 9 12
A Module 1, phase
3
0 0.1 0.2
Chapter 5
Configuring the Power Distribution Units
5-23