Table 5-9 Threshold Values for Oracle Exadata Database Machine X4-2 Quarter
Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 10 13
A Module 1, phase
2
0 5 7
A Module 1, phase
3
0 0.1 0.2
B Module 1, phase
1
0 0.1 0.2
B Module 1, phase
2
0 5 7
B Module 1, phase
3
0 10 13
Table 5-10 (page 5-25) lists the threshold values for Oracle Exadata Database
Machine X4-2 Quarter Rack using a three-phase, low-voltage PDU.
Table 5-10 Threshold Values for Oracle Exadata Database Machine X4-2
Quarter Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 11 14
A and B Module 1, phase
2
0 10 13
A and B Module 1, phase
3
0 5 7
Table 5-11 (page 5-25) lists the threshold values for Oracle Exadata Database
Machine X4-2 Quarter Rack using a single-phase, high-voltage PDU.
Table 5-11 Threshold Values for Oracle Exadata Database Machine X4-2
Quarter Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 9 12
A Module 1, phase
2
0 5 7
A Module 1, phase
3
0 0.1 0.2
Chapter 5
Configuring the Power Distribution Units