Table 1-6 Environmental Requirements for Oracle Exadata Database Machine
X3-2
Environmental
Component
Oracle Exadata
Database
Machine X3-2
Full Rack
Oracle Exadata
Database
Machine X3-2
Half Rack
Oracle Exadata
Database
Machine X3-2
Quarter Rack
Oracle Exadata
Database
Machine Eighth
Rack
Weight
See Also:
"Flooring
Requirements
(page 1-34)"
871.4 kg (1921
lbs)
543.9 kg (1199
lbs)
368.8 kg (813
lbs)
368.8 kg (813
lbs)
Acoustic levels 87 db(A) 84 db(A) 81 db(A) 81 db(A)
Power
See Also:
"Electrical Power
Requirements
(page 1-34)"
• High
performance
drives
Maximum:
12.1 kVA
Typical: 8.6
kVA (varies
based on
application
load)
• High
capacity
drives
Maximum:
11.1 kVA
Typical: 7.8
kVA (varies
based on
application
load)
• High
performance
drives
Maximum:
6.6 kVA
Typical: 4.7
kVA (varies
based on
application
load)
• High
capacity
drives
Maximum:
6.1 kVA
Typical: 4.3
kVA (varies
based on
application
load)
• High
performance
drives
Maximum:
3.3 kVA
Typical: 2.4
kVA (varies
based on
application
load)
• High
capacity
drives
Maximum:
3.1 kVA
Typical: 2.2
kVA (varies
based on
application
load)
• High
performance
drives
Maximum:
3.0 kVA
Typical: 2.1
kVA (varies
based on
application
load)
• High
capacity
drives
Maximum:
2.8 kVA
Typical: 2.0
kVA (varies
based on
application
load)
Chapter 1
General Environmental Requirements
1-12

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle EXADATA X6-2 and is the answer not in the manual?

Oracle EXADATA X6-2 Specifications

General IconGeneral
BrandOracle
ModelEXADATA X6-2
CategoryServer
LanguageEnglish

Related product manuals