Table 1-6 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X3-2
Environmental
Component
Oracle Exadata
Database
Machine X3-2
Full Rack
Oracle Exadata
Database
Machine X3-2
Half Rack
Oracle Exadata
Database
Machine X3-2
Quarter Rack
Oracle Exadata
Database
Machine Eighth
Rack
Cooling
See Also:
"Temperature
and Humidity
Requirements
(page 1-44)",
and "Ventilation
and Cooling
Requirements
(page 1-45)"
• High
performance
drives
Maximum:
40,600 BTU/
hour (42,800
kJ/hour)
Typical:
28,700 BTU/
hour (30,300
kJ/hour)
• High
capacity
drives
Maximum:
37,200 BTU/
hour (39,250
kJ/hour)
Typical:
26,000 BTU/
hour (27,400
kJ/hour)
• High
performance
drives
Maximum:
22,200 BTU/
hour (23,400
kJ/hour)
Typical:
15,700 BTU/
hour (16,600
kJ/hour)
• High
capacity
drives
Maximum:
20,500 BTU/
hour (21,600
kJ/hour)
Typical:
14,300 BTU/
hour (15,100
kJ/hour)
• High
performance
drives
Maximum:
10,900 BTU/
hour (11,500
kJ/hour)
Typical:
7,850 BTU/
hour (8,300
kJ/hour)
• High
capacity
drives
Maximum:
10,200 BTU/
hour (10,800
kJ/hour)
Typical:
7,200 BTU/
hour (7,600
kJ/hour)
• High
performance
drives
Maximum:
9,900 BTU/
hour (10,500
kJ/hour)
Typical:
6,800 BTU/
hour (7,200
kJ/hour)
• High
capacity
drives
Maximum:
9,200 BTU/
hour (9,700
kJ/hour)
Typical:
6,500 BTU/
hour (6,850
kJ/hour)
Air flow front-to-
back (subject to
actual data
center
environment)
See Also:
"Temperature
and Humidity
Requirements
(page 1-44)",
and "Ventilation
and Cooling
Requirements
(page 1-45)"
• High
performance
drives
Maximum:
Approximatel
y 1,900 CFM
Typical:
Approximatel
y 1,350 CFM
• High
capacity
drives
Maximum:
Approximatel
y 1,700 CFM
Typical:
Approximatel
y 1,200 CFM
• High
performance
drives
Maximum:
Approximatel
y 1,050 CFM
Typical:
Approximatel
y 750 CFM
• High
capacity
drives
Maximum:
Approximatel
y 950 CFM
Typical:
Approximatel
y 670 CFM
• High
performance
drives
Maximum:
Approximatel
y 500 CFM
Typical:
Approximatel
y 375 CFM
• High
capacity
drives
Maximum:
Approximatel
y 470 CFM
Typical:
Approximatel
y 330 CFM
• High
performance
drives
Maximum:
Approximatel
y 460 CFM
Typical:
Approximatel
y 325 CFM
• High
capacity
drives
Maximum:
Approximatel
y 425 CFM
Typical:
Approximatel
y 300 CFM
Chapter 1
General Environmental Requirements
1-13