Table 5-21 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 10 13
A Module 1, phase
2
0 5 6
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 5 6
B Module 1, phase
3
0 10 13
Table 5-22 (page 5-31) lists the threshold values for Oracle Exadata Database
Machine X3-2 Quarter Rack using a three-phase, low-voltage PDU.
Table 5-22 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 11 14
A and B Module 1, phase
2
0 10 13
A and B Module 1, phase
3
0 4 6
Table 5-23 (page 5-31) lists the threshold values for Oracle Exadata Database
Machine X3-2 Quarter Rack using a single-phase, high-voltage PDU.
Table 5-23 Threshold Values for Oracle Exadata Database Machine X3-2
Quarter Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 9 11
A Module 1, phase
2
0 4 6
A Module 1, phase
3
0 0 0
Chapter 5
Configuring the Power Distribution Units