• Table 5-25 (page 5-33) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Full Rack with Single-phase, Low-
voltage PDU
• Table 5-26 (page 5-33) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Full Rack with Three-phase, Low-
voltage PDU
• Table 5-27 (page 5-34) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Full Rack with Single-phase, High-
voltage PDU
• Table 5-28 (page 5-34) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Full Rack with Three-phase, High-
voltage PDU
Table 5-25 (page 5-33) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a single-phase, low-voltage PDU.
Table 5-25 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Full Rack with Single-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 18 23
A Module 1, phase
2
0 22 24
A Module 1, phase
3
0 18 23
B Module 1, phase
1
0 18 23
B Module 1, phase
2
0 22 24
B Module 1, phase
3
0 18 23
Table 5-26 (page 5-33) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, low-voltage PDU.
Table 5-26 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Full Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 32 40
A and B Module 1, phase
2
0 34 43
A and B Module 1, phase
3
0 33 42
Chapter 5
Configuring the Power Distribution Units
5-33