Table 5-38 (page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, low-voltage PDU.
Table 5-38 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 36 45
A and B Module 1, phase
2
0 39 44
A and B Module 1, phase
3
0 38 45
Table 5-39 (page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a single-phase, high-voltage PDU.
Table 5-39 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 20 21
A Module 1, phase
2
0 20 21
A Module 1, phase
3
0 19 21
B Module 1, phase
1
0 19 21
B Module 1, phase
2
0 20 21
B Module 1, phase
3
0 20 21
Table 5-40 (page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, high-voltage PDU.
Table 5-40 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Three-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 20 21
A and B Module 1, phase
2
0 21 21
A and B Module 1, phase
3
0 18 21
Chapter 5
Configuring the Power Distribution Units
5-40