Table 5-42 (Cont.) Threshold Values for Oracle Exadata Database Machine X2-2
(with X4170 and X4275 servers) Half Rack with Three-phase, Low-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
2
0 20 25
A and B Module 1, phase
3
0 19 24
Table 5-43 (page 5-42) lists the threshold values for Oracle Exadata Database
Machine Half Rack using a single-phase, high-voltage PDU.
Table 5-43 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Half Rack with Single-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A Module 1, phase
1
0 19 21
A Module 1, phase
2
0 12 15
A Module 1, phase
3
0 0 0
B Module 1, phase
1
0 0 0
B Module 1, phase
2
0 12 15
B Module 1, phase
3
0 19 21
Table 5-44 (page 5-42) lists the threshold values for Oracle Exadata Database
Machine Half Rack using a three-phase, high-voltage PDU.
Table 5-44 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Half Rack with Three-phase, High-voltage PDU
PDU Module/Phase Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B Module 1, phase
1
0 11 14
A and B Module 1, phase
2
0 11 14
A and B Module 1, phase
3
0 10 13
Chapter 5
Configuring the Power Distribution Units
5-42

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle EXADATA X6-2 and is the answer not in the manual?

Oracle EXADATA X6-2 Specifications

General IconGeneral
BrandOracle
ModelEXADATA X6-2
CategoryServer
LanguageEnglish

Related product manuals