1.1.14 General Environmental Requirements for Oracle Exadata
Storage Expansion Rack X4-2
The environmental requirements for Oracle Exadata Storage Expansion Rack X4-2
depend on the size of the system. Table 1-12 (page 1-22) shows the general
environmental requirements for each type of Oracle Exadata Storage Expansion Rack
X4-2.
Table 1-12 Environmental Requirements for Oracle Exadata Storage Expansion
Rack X4-2
Environmental
Component
Oracle Exadata
Storage Expansion
X4-2 Full Rack
Oracle Exadata
Storage Expansion
X4-2 Half Rack
Oracle Exadata
Storage Expansion
X4-2 Quarter Rack
Weight 824.2 kg (1817 lbs) 513.0 kg (1131 lbs) 346.5 kg (764 lbs)
Acoustic levels 82 db(A) 79 db(A) 76 db(A)
Power High performance
drives
Maximum: 10.2
kVA
Typical: 7.1 kVA
(varies based on
application load)
High capacity
drives
Maximum: 9.1
kVA
Typical: 6.3 kVA
(varies based on
application load)
High performance
drives
Maximum: 5.7
kVA
Typical: 4.1 kVA
(varies based on
application load)
High capacity
drives
Maximum: 5.2
kVA
Typical: 3.7 kVA
(varies based on
application load)
High performance
drives
Maximum: 2.9
kVA
Typical: 2.0 kVA
(varies based on
application load)
High capacity
drives
Maximum: 2.7
kVA
Typical: 2.0 kVA
(varies based on
application load)
Cooling High performance
drives
Maximum: 34,100
BTU/hour (36,000
kJ/hour)
Typical: 23,900
BTU/hour (25,200
kJ/hour)
High capacity
drives
Maximum: 30,400
BTU/hour (32,100
kJ/hour)
Typical: 21,200
BTU/hour (22,400
kJ/hour)
High performance
drives
Maximum: 19,100
BTU/hour (20,150
kJ/hour)
Typical: 13,650
BTU/hour (14,400
kJ/hour)
High capacity
drives
Maximum: 17,400
BTU/hour (18,400
kJ/hour)
Typical: 12,300
BTU/hour (13,000
kJ/hour)
High performance
drives
Maximum: 9,500
BTU/hour (10,000
kJ/hour)
Typical: 6,700
BTU/hour (7,000
kJ/hour)
High capacity
drives
Maximum: 8,900
BTU/hour (9,400
kJ/hour)
Typical: 6,500
BTU/hour (6,900
kJ/hour)