Troubleshooting PACD011001C2
186 Troubleshooting Urban Multi “MX1, ME1 Series” Using R-22
3.31 Malfunction of Transmission between Master and Slave Remote Controllers
Remote Controller
Display
U8
U8U8
U8
Supposed Causes
„
Malfunction of transmission between master and slave remote controller
„
Connection between sub remote controllers
„
Defect of remote controller PC board
Troubleshooting
(VF057)
SS1
of both remote controllers is set
to "SLAVE."
Set SS1 to "MASTER"; the power
supply off once and then back on.
Set one remote controller to
"MASTER"; the power supply off
once and then back on.
Turn the power off and then back
on. If a malfunction occurs,
replace the remote controller PC
board.
YES
YES
YES
NO
NO
NO
Using 2-remote controllers
control.
SS1 of remote
controller PC boards is set to
"MASTER."
Caution
Be sure to turn off power switch before connect or disconnect connector,