Troubleshooting PACD011001C2
186 Troubleshooting Urban Multi “MX1, ME1 Series” Using R-22
3.31 Malfunction of Transmission between Master and Slave Remote Controllers
Remote Controller
Display
U8
U8U8
U8
Supposed Causes
Malfunction of transmission between master and slave remote controller
Connection between sub remote controllers
Defect of remote controller PC board
Troubleshooting
(VF057)
SS1
of both remote controllers is set
to "SLAVE."
Set SS1 to "MASTER"; the power
supply off once and then back on.
Set one remote controller to
"MASTER"; the power supply off
once and then back on.
Turn the power off and then back
on. If a malfunction occurs,
replace the remote controller PC
board.
YES
YES
YES
NO
NO
NO
Using 2-remote controllers
control.
SS1 of remote
controller PC boards is set to
"MASTER."
Caution