PACD011001C2 Troubleshooting
Troubleshooting Urban Multi “MX1R, ME1R Series” Using R-407C 375
3.32 Malfunction of Transmission Between Indoor and Outdoor Units in the Same
System
Remote Controller
Display
U9
U9U9
U9
Supposed Causes
„
Malfunction of transmission between indoor and outdoor of other system
„
Malfunction of electronic expansion valve in indoor unit of other system
„
Defect of PC board of indoor unit in other system
„
Improper connection of transmission wiring between indoor and outdoor unit
Troubleshooting
(VF058)
The "U4"
display blinks on
the remote controllers of other
units within the same
refrigerant
system.
Refer to failure diagnosis for "U5"
malfunction code.
Re-diagnose by display after passage
of 2 minutes or more.
Refer to failure disgnosis for "UA"
malfuntion code.
NO
NO
NO
NO
Refer to failure diagnosis for "U4"
malfunction code.
YES
YES
YES
"U9"
has been displayed for 2
minutes or more.
Turn on all indoor units.
Refer to failure diagnosis for "A1"
malfunction code.
NO
YES
The "A1"
display blinks on
the remote controllers of other
units within the same
refrigerant
system.
The "UA"
display blinks on
the remote controllers of other
units within the same
refrigerant
system.
Refer to failure diagnosis for "A9"
malfunction code.
NO
YES
The "A9"
display blinks on
the remote controllers of other
units within the same
refrigerant
system.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.