PACD011001C2 Function
Function Urban Multi “MX1, ME1 Series” Using R-22 37
1.10 Frequency Limit Control by Pressure Equalization (ME1 Series)
The compressor operating capacity is limited to prevent abnormal noise caused by the equalizing
operation.
Operating conditions
During the first 30 seconds, the following operations are conducted.
&
Equalizing operation demand issued
Not in cooling operation only
INV outdoor unit
Compressor operating capacity 54Hz + OFF