PACD011001C2 Troubleshooting
Troubleshooting Urban Multi “MX1R, ME1R Series” Using R-407C 351
3.8 Indoor Unit: Malfunction of Capacity Determination Device
Remote controller
display
AJ
AJAJ
AJ
Supposed Causes
You have forgotten to install the capacity setting adaptor.
Defect of indoor unit PC board
Troubleshooting
(VF035)
Install a capacity setting adaptor.
Replace the indoor unit PC board.
NO
NO
YES
YES
Replace the indoor unit PC board.
The indoor
unit PC board was replaced
with a replacement
PC board.
The indoor
unit is a model that
requires installation of a
capacity setting adaptor when
replacing the PC
board.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.