EasyManua.ls Logo

Panasonic CU-8ME1XPK - Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature Rise Sensor

Panasonic CU-8ME1XPK
643 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PACD011001C2 Troubleshooting (Inverter)
Troubleshooting Urban Multi “MX1, ME1 Series” Using R-22 201
5.8 Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Remote Controller
Display
P4
P4P4
P4
Supposed Causes
Defect of radiator fin temperature sensor
Defect of inverter unit
Troubleshooting
(VF070)
Replace the radiator fin
thermistor.
Turn on again after letting 30
minutes or more pass after
occurrence of malfunction.
"P4" occurs again.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.

Table of Contents

Other manuals for Panasonic CU-8ME1XPK

Related product manuals