PACD011001C2 Function
Function Urban Multi “MX1R, ME1R Series” Using R-407C 245
1.6 Equalized Oil Level Operation
(Equalized Oil Level between Twin Compressors)
If using two compressors (8, 10Hp) connected in parallel, oil level equalizing is carried out for 5 minutes if
the cumulative running time of the standard compressor exceeds 2 hours in order to prevent lack of oil
cause by difference in pressure inside the dome due to drift, and then reverts to normal operation.
If oil pressure equalization is not achieved during 5 minutes by stopping or step down control, oil
pressure equalization is carried out when the standard compressor starts running.
With an inverter compressor operation, however, if the standard compressor remains off for 10 minutes,
the cumulative running time of the standard compressor is reset.
During equalized oil level operation with Y2R
ON, when low pressure < 2.0kg/cm², Y2S becomes ON.
(Reset at low pressure > 3.0kg/cm²)
Inverter compressor Standard compressor
106Hz OFF