Product Outline PACD011001C2
410 General Information UM Combination “MA1R Series” Using R-407C
Other versatile
functions are
provided
Individual control of up to 20 indoor units with one 20HP class outdoor unit
For Urban Multi Combination
Others
High efficiency with power factor of 90% or higher
Cooling operation with outdoor air temperature as low as –5°C
Heating operation with outdoor air temperature as low as –15°C
Simple Branch piping system
Super wiring system
Automatic address setting function
Built-in wiring error check function
Equipped with sequential start function
Nighttime low-noise mode for reduced operating sound
Long refrigerant piping : equivalent
length of 125, actual length of 100 m
and height difference of 50 m.
Connection of indoor unit of varying
capacities and types totaling 130%
(max.) of outdoor unit by capacity.
Outdoor unit name No. of indoor units connectable
PA-16~20MA 20 units
PA-24~30MA 32 units
Height difference
between indoor units
15m
100m
Actual height difference
between indoor unit and
outdoor unit
50 m
40 m
from first Branch
to last indoor unit.
(In case of the outdoor
unit located upper position
than the indoor unit)
(V0804)
(V0805)