Outline of Control PACD011001C2
444 Function UM Combination “MA1R Series” Using R-407C
3.1.19 Fan Location and Fan Tap
Fan Location
Fan Tap Table
M2F
(1 speed)
230W
M1F
(2 speed)
140W
M4F
(1 speed)
230W
M3F
(1 speed)
140W
M4F
(1 speed)
230W
M12F
(1 speed)
230W
M11F
(2 speed)
140W
M22F
(1 speed)
230W
M21F
(1 speed)
140W
M3F
(1 speed)
140W
Master Unit Sub Unit
Master Unit Sub Unit
(INV)
(INV)
(16~20HP)
(24~30HP)
(V0846)
tap
16~20HP 24~30HP
M1F M2F M3F M4F M11F M12F M21F M22F M3F M4F
OFF +OFF /OFF +OFF OFF +OFF +OFF +OFF /OFF +OFF
1
L +OFF /OFF +OFF L +OFF +OFF +OFF /OFF +OFF
2
H +OFF /OFF +OFF H +OFF +OFF +OFF /OFF +OFF
3
H+OFF+ON +OFF H+OFF+ON +OFF +ON +OFF
4
H +ON +ON +OFF H +ON +ON +OFF +ON +OFF
5
H +ON +ON +ON H +ON +ON +ON +ON +ON
Tfin > 87°C
↓ ↑
Tfin < 67°C
tap
24~30HP
M11F M12F M21F M22F M3F M4F
’OFF
+ON +OFF +OFF /OFF +OFF
1’ OFF
+ON +OFF +OFF /OFF +OFF
2’ OFF
+ON +OFF +OFF /OFF +OFF
3’ OFF
+ON +ON +OFF +ON +OFF
4’ H +ON +ON +OFF +ON +OFF
5’ H +ON +ON +ON +ON +ON