PACD011001C2 Function
Function Urban Multi “MX1, ME1 Series” Using R-22 41
Outdoor Unit
Function
Notes
„
During defrost or oil return, residual operation is not carried out even if a stop command comes.
„
Forced thermostat OFF occurs if defrost or oil return signal comes during residual operation.
Outdoor air (R1T) Compressor Electronic expansion
valve
Time
INV STD
R1T < -10°C 86Hz OFF 0~300 pulses 10 min.
-10°C
≤
R1T < 0°C 76Hz OFF 0~300 pulses 10 min.
R1T
≥
0°C 60Hz OFF 0~300 pulses 10 min.