PACD011001C2 Function
Function Urban Multi “MX1, ME1 Series” Using R-22 53
1.20.3 When the Float Switch is Tripped during Heating Operation:
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5 seconds stop,
5 minutes operation cycle ends, operation continues until the switch is reset.
1.20.4 When the Float Switch is Tripped and “AF” is Displayed on the Remote Controller:
Note:
If the float switch is tripped five times in succession, a drain malfunction is determined to have occurred.
“AF” is then displayed as operation continues.