Communication 
 
FPΣ User's Manual 
170 
Adjusting the response time of the external device (when using FPG-COM4) 
The RS485 port of FPG-COM4 occupies the communication line for a certain period of time 
after sending data. During this time, data cannot be received from another device. Therefore, 
the connected device should not send a response to the FPΣ before the time t indicated below 
has passed. 
FPG-COM4
tt
 
1
 
External device 
Send data 
t 
Response time 
Send response 
 
Baud rate  Response time 
19200bit/s  t > 1ms 
115200bit/s 
t > 200μs 
Make the following adjustments depending on the communication mode and the connected 
device: 
1. FPΣ using FPG-COM4: 
-  PLC Link: No adjustments required. 
-  Program controlled: Adjust t in the program algorithm. 
-  MEWTOCOL-COM Master/Slave: Adjust t using the SYS1 instruction (see above) 
2.  Other PLCs from Panasonic: 
-  PLC Link: Adjustment not possible. 
-  Program controlled: Adjust t in the program algorithm. 
3. Computer:  
-  Adjust t in the program algorithm using a WAIT instruction. 
4. Others: 
-  Information about the time t (time after which the device starts to respond when 
data has been received) can be obtained from the device manufacturer. 
-  KT temperature controllers and inverters (e.g. VF-7E, VF-8X) can be used without 
any adjustments because t ≥ 1ms. 
-  GT Series terminals cannot be used.