FPΣ User's Manual 
 
11.2 Operation on Error 
263 
11.2  Operation on Error 
The CPU has a self-diagnostic function which identifies errors and stops operation if 
necessary. For some errors, the user may select whether operation shall continue or stop 
when the error occurs. 
 
1.
2.
3.
Procedure
 
1.  Double-click "PLC" in the navigator 
2.  Double-click "System Registers" 
3.  Double-click “Act on Error” 
Select the desired setting for each type of error. 
 
EXAMPLE
 
1.  Operation is to continue even though a calculation error has occurred:  
Set system register no. 26 "Operation error" to "Continue". Operation errors will 
be handled as an error, but operation will continue. 
2.  When using a battery, a battery error is to be indicated in the PLC Status 
dialog and by an LED: 
Set system register no. 4 "Batter error indication" to "Enable". When the battery 
voltage drops, the ERROR/ALARM LED will flash.