Connector
pin No.
(Note 2)
Turns on the output transistor during
servo on.
Position
comparison output
The output transistor is turned ON or
OFF when the actual position passes
the position set by the parameter.
Deterioration
diagnosis velocity
output
Output transistor turned ON when
motor speed is within the range of
Pr4.35 “Speed coincidence range” of
Pr5.75 “Deterioration diagnosis
velocity setting”.
There is a hysteresis of 10r/min in
the coincidence judgment of
deterioration diagnosis velocity.
(Note 1) For the signal with “-” sign in the “Related control mode” column, the output transistor is always turned off in that control mode.
(Note 2) Output pin assignment can be changed. The pins in “Connector pin No.” column in the table denote factory default settings. The
signal with a pin that is marked with “*” is not assigned by default.
For more information, refer to “ 2.4.2 Output signal allocation”.
(Note 3) It is possible to monitor the condition of the signals where “✔” is attached to the EtherCAT communication monitor on the table
with 2322h/2722h (Logical output signal) or 60FDh/68FDh (Digital inputs).
(Note 4) The state of output transistor changes as follows in each EtherCAT communication state:
Setting value of
60FEh/68FEh
State of output transistor (SO1/SO2)
Communication
established
(Note 5)
Communication
intercepted
(Note 5)
Communication
re-established
(Note 5)
bit0 = 1
(initialization)
(Note 5) “Communication established”, “Communication intercepted”, and “Communication re-established” refer to the following cases.
Communication established
ESM state is PreOP or higher
Communication intercepted
PDO communication is disabled(ESM state transitioned to other states than OP), or SDO
communication is disabled(ESM state transitioned to Init)
Communication re-established
60FEh-01h or 60FEh-02h has been written successfully
(Note 6) Pr4.59 (Mechanical brake signal setting) sets the mechanical brake signal output from the mechanical brake output (BRK +/-)
and does not affect the set brake output from SO1 / SO2.
Safety precautions:
When executing set brake signal control using 60FEh/68FDh (Digital outputs), be sure to
use it in PDO and enable the PDO watch dog.
In SDO, the communication shutoff cannot be judged, the brake may be kept to be released
and it is unsafe.
Please ensure safety on the equipment side.