2.2I/O connector output signal
2-7
(Note 7) The general-purpose output 1 (EX-OUT1) can be replaced with the contactor output (MC-OUT) of the power supply module only
for the Axis A of the driver module with the inter-module communication node address set to 1.
In addition, the following parameter settings are required:
<Relevant parameters>
Communication
function extended
setup 3
bit 0 : EX-OUT1 output (MC-OUT output) setting when
EtherCAT communication is cut off
0: Hold output when communication is interrupted
1: Output initialization (OFF) when communication
is cut off
* The output will be OFF regardless of this setting until
the EtherCAT communication is established after the
power is turned on.
Communication
function extended
setup 5
bit1: Power supply module contactor output switching
0: Use EX-OUT1 with general-purpose output 1
1: EX-OUT1 is used as the contactor output
(MC-OUT).
* This setting is valid only for the Axis A parameter of the
driver module whose module communication node
address is 1.
When the control power is turned on with the above settings, the contactor output (MC-OUT) of the power supply module can be
operated with the Axis A object 60FEh (Digital outputs) of the driver module with the inter-module communication node address
set to 1.
Setting value of
60FEh (Axis A)
State of output relay (PSM X101 connector MC1/MC2)
Communication
established
(Note 5)
Communication
intercepted
(Note 5)
Communication
re-established
(Note 5)
MC-OUT = 0
(Relay open, hold)
MC-OUT = 1
(Relay short, hold)
bit0 = 1
(initialization)