2.4.1.2 Reallocation of input signal
To change the allocation of input signal, change the following parameters.
Relevant parameters
Class
No.
Attribute
Parameter
name
Unit
Range
Function
Latch
correction
function
4
00
C
S
SI1 input
selection
-
-2147483648
to
2147483647
Assign functions to SI1 inputs.
These parameters are presented in hexadecimals.
Hexadecimal presentation is followed by a specific
control mode designation.
n 0 * * h: position/full-closed control
n 0 * * h: velocity control
n 0 * * h: torque control
(1) Replace "**" with the function number. Refer to
the Input function number table. Both signal and
logic are involved a function number.
(2) Set axis selection to input in 4bit (bit31 to 28) of
"n"
n=0 (Axis A)
Only the Axis A accepts input signals.
n=2 (Axis B)
nly the Axis B accepts input signals.
n=6 (A or B)
Both Axis A and Axis B accept input
signals.
Do not specify any other settings.
Example 1)
When SI6 pin is specified as POT b-contact and
assigned to Axis A,
set Pr4.05 to 00818181h
Example 2)
When SI1 pin is specified as HOME a-contact and
assigned to Axis B,
set Pr4.00 to 00222222h
Example 3)
When SI8 pin is specified as E-STOP b-contact
and assigned to both Axis A and Axis B,
set Pr4.07 to 60949494h
This pin has a latch correction function for Axis B.