Technical Specifications 9-17
650V AC Drive
Supply Harmonic Analysis (Frame D Normal Duty)
Assumptions: 10000A short circuit supply capability, equivalent
to 73µH supply impedance at 400V where Q
1n
is the rated rms
value of the fundamental voltage of the supply transformer. The
results conform to stage 1, stage 2 and stage 3 of the
Engineering Recommendation G.5/3 September 1976,
Classification ‘C’: Limits for Harmonics in the UK Electricity
Voltage (V)
230 400 500
Motor Power
11.0 15.0 18.0 15.0 18.0 22.0 30.0 15.0 18.0 22.0 30.0
Typical
Motor
Efficiency %
90 90
90 90 90 90 90 90 90 90
No.
RMS Current (A)
47.2 59.2
30.6 36.3 48.2 67.7 23.4 29.0 38.6
*
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.1 0.0
22.5 23.3
21.6 24.8 31.0 41.7 17.6 20.9 26.6
12.5 11.5
14.7 16.4 19.6 25.5 13.0 14.7 17.8
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
3.3 4.4
3.7 3.6 3.4 4.0 4.5 4.2 4.1
2.7 3.0
2.0 2.4 3.3 4.7 2.1 2.1 2.6
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
1.8 2.5
1.7 1.8 1.8 2.1 1.6 1.8 2.0
1.3 1.7
1.1 1.1 1.4 1.9 1.3 1.3 1.2
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
1.2 1.6
0.9 1.0 1.0 1.3 0.6 0.8 1.1
0.9 1.2
0.7 0.8 0.8 1.1 0.6 0.8 0.8
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.8 1.1
0.5 0.6 0.6 0.9 0.4 0.4 0.6
0.7 0.9
0.5 0.5 0.6 0.7 0.4 0.4 0.5
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.6 0.8
0.3 0.3 0.4 0.6 0.3 0.3 0.4
0.5 0.7
0.3 0.3 0.5 0.5 0.3 0.3 0.4
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.4 0.6
0.2 0.2 0.2 0.5 0.2 0.2 0.3
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.4 0.5
0.2 0.2 0.4 0.4 0.2 0.2 0.2
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.3 0.4
0.2 0.2 0.2 0.3 0.1 0.2 0.2
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.3 0.4
0.2 0.2 0.3 0.3 0.1 0.2 0.2
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
Total RMS
54.0 65.0
40.5 47.2 60.8 83.8 32.6 39.1 50.5
0.97 1.05 0.96 1.08 1.30 1.72 0.85 0.96 1.16